IS 158112008AI Search Enabled✦ AI Generated

IS 15811 — Long-range water-cum-foam monitor with self-inducting, aspirating and non-aspirating jet and spray/fog nozzle forfire fighting -Specification

IS 15811:2008 specifies requirements for long-range water-cum-foam monitors equipped with self-inducting, aspirating, and non-aspirating jet and spray/fog nozzles used in fire fighting. Applicable to stand post or trolley/trailer mounted monitors with nominal sizes from 63 mm to 150 mm, this standard covers construction, materials, performance, and testing to ensure effective foam and water discharge for Class B flammable liquid fire protection. It is essential for manufacturers, engineers, and safety professionals involved in fire suppression system design and maintenance.

13Sections
42Clauses Indexed
✓AI Search Ready
2008Edition
Fire FightingCategory
Alternative search terms: IS 15811 PDF, IS 15811 pdf free download, IS 15811 free download pdf, IS15811 PDF, IS-15811 PDF, IS 15811 2008 PDF, IS 15811:2008 PDF, IS 15811-2008 PDF, IS 15811 (2008) PDF, IS 15811 2008 edition PDF, IS 15811 edition 2008 PDF

What This Standard Covers

IS 15811:2008 specifies requirements for long-range water-cum-foam monitors equipped with self-inducting, aspirating, and non-aspirating jet and spray/fog nozzles used in fire fighting. Applicable to stand post or trolley/trailer mounted monitors with nominal sizes from 63 mm to 150 mm, this standard covers construction, materials, performance, and testing to ensure effective foam and water discharge for Class B flammable liquid fire protection. It is essential for manufacturers, engineers, and safety professionals involved in fire suppression system design and maintenance.

Who Uses This Standard

  • Fire protection engineers
  • Fire safety equipment manufacturers
  • Industrial safety officers
  • Fire brigade and emergency responders
  • Mechanical design engineers
  • Quality assurance professionals in fire safety
  • Procurement specialists for fire fighting equipment

Key Topics Covered

✓Design and construction of water-cum-foam monitors
✓Material specifications for components
✓Types of nozzles: aspirating and non-aspirating
✓Jet and spray/fog nozzle performance
✓Horizontal and vertical traversing mechanisms
✓Hydraulic pressure and leakage testing
✓Foam concentrate induction and jet ratio control
✓Corrosion protection and anti-corrosive treatments
✓Performance requirements including flow rates and reach
✓Marking and certification requirements
✓Compatibility with sea water usage
✓Accessories and operational features

Table of Contents

1Scope▼

IS 15811: Scope - Key Specifications & Tables

Scope: Covers performance, construction, and testing of water foam monitors used in firefighting.


Key Performance Requirements (Clause 9)

  • Test Pressure: 0.7 N/mm² at monitor inlet flange.
  • Induction Rate:
    • 3% induction: 3–4% actual
    • 6% induction: 6–7% actual
  • Expansion Ratio:
    • Non-aspirating: ≥ 1:4
    • Aspirating: ≥ 1:6 (measured per IS 4989)
  • Spray/Fog Angle: Minimum 120°
  • Flow Tolerance: Total flow ±5%, induction rate as above.
  • Jet Ratio Controller Test: Hydraulic test at 2.3 N/mm² for 5 min, no leakage (Clause 8.2).

Table 2: Minimum Performance Requirements (Excerpt)

Monitor Size (mm)Water Discharge (LPM) at 0.7 N/mm²Min Effective Water Reach (m)Min Effective Foam Reach (m)
6317505345
10035006456
150100008274

Note: For aspirating types, reduce reach by 10%.


Construction Materials (Table 1 Highlights)

ComponentCarbon SteelStainless SteelCopper Alloy
Inlet flangeIS 2002 Gr. IIS 6911IS 318 Gr. LTB-II
NozzleIS 617 Gr 4450/4225IS 3444IS 318 LTB-II
Worm shaftStainless SteelStainless SteelStainless Steel

Summary Diagram: Monitor Testing & Performance

flowchart LR
    A[Water Foam Monitor] --> B[Test at 0.7 N/mm²]
    B --> C{Parameters}
    C --> D[Flow & Induction Rate]
    C -->
2Referenced Indian Standards▼

IS 15811 - Referenced Indian Standards: Key Points

  • Clause 12.2.1 governs the use of BIS Standard Mark as per the Bureau of Indian Standards Act, 1986.
  • ANNEX A lists Indian Standards referenced in IS 15811, critical for materials, dimensions, and specifications.
IS No.Title
IS 5:2004Colours for ready mixed paints and enamels
IS 28:1985Phosphor bronze ingots and castings
IS 210:1993Gray iron castings - Specification
IS 291:1989Naval brass rods and sections for machining purposes
IS 2002:1992Steel plates for pressure vessels (intermediate & high temp)
IS 2643:2005Pipe threads where pressure-tight joints are not made
IS 617:1994Aluminium and aluminium alloy ingots and castings
IS 3444:1999Corrosion resistant high alloy steel and nickel base castings
IS 778:1984Copper alloy gate, globe and check valves for water works
IS 1239:1990Steel tubes and fittings specification
IS 4989:2006Foam concentrate for mechanical foam for fire fighting
IS 6911:1992Stainless steel plate, sheet and strip
IS 1732:1989Dimensions for round and square steel bars

Rounding Off: As per IS 2:1960, numerical values must be rounded off maintaining the same significant figures as specified.


Summary Diagram of Reference Flow

graph LR
A[IS 15811] --> B[Material Specs]
A --> C[Dimensions & Tolerances]
A --> D[Marking & Certification]
B --> IS5[IS 5:2004 Paint Colors]
B --> IS28[IS 28:1985 Bronze]
C --> IS1732[IS 1732:1989 Steel Bars]
D --> BISAct[BIS Act 1986]

For detailed specifications, consult each referenced IS document via BIS website or offices.

3Terminology and Definitions▼

IS 15811: Terminology and Definitions - Key Points

  • Rounding Off (IS 2:1960): Final test or calculation values must be rounded to the same significant figures as the specified values in the standard.

  • Leakage Test (Clause 8.2): Jet ratio controller (if present) is hydraulically tested at 2.3 N/mm² for 5 minutes with no leakage allowed.

  • Performance Requirements (Clause 9):

    • Test pressure: 0.7 N/mm² at monitor inlet flange.
    • Flow and foam induction rate:
      • Induction rate for 3% requirement: 3% to 4%
      • Induction rate for 6% requirement: 6% to 7%
    • Expansion ratio (per IS 4989):
      • Non-aspirating: min 1:4
      • Aspirating: min 1:6
    • Spray/fog angle: minimum 120°
    • Flow tolerance: total flow within +5% / -0%
  • Minimum Horizontal Reach & Flow Capacity (Table 2):

Monitor Size (mm)Water Discharge (LPM)Effective Water Reach (m)Effective Foam Reach (m)
6317505345
752580 - 300060 - 6252 - 54
1003500 - 415064 - 6856 - 60
1504750 - 1250069 - 9061 - 80

Note: Aspirating type reach is 10% less than values above.

  • Paint Color: Fire red as per IS 5 shade No. 536 or 538; paint to conform to IS 2932.

Summary Diagram of Performance Parameters

flowchart LR
    A[Water Foam Monitor] --> B[Inlet Pressure: 0.7 N/mm²]
    B --> C[Flow Rate: Specified LPM]
    C --> D[Induction Rate: 3-
4Materials of Construction▼

IS 15811: Materials of Construction for Water Foam Monitors

Key Specifications (Clause 4.1 & Table 1)

ComponentCarbon Steel WaterwayStainless Steel WaterwayCopper Alloy Waterway
Inlet flangeIS 2002 Gr. I / IS 2004IS 6911IS 318 Gr. LTB-II / IS 28 Gr. II
ReducerIS 1239 (Part 2), IS 11428Stainless SteelIS 318 Gr. LTB-II / IS 28 Gr. II
Elbow/BendIS 4310Stainless SteelIS 318 Gr. LTB-II / IS 28 Gr. II
Swivel joint & worm wheelIS 318 LTB-II, IS 28 Gr. IIStainless SteelIS 318 Gr. LTB-II / IS 28 Gr. II
Worm shaftStainless SteelStainless SteelStainless Steel
Manual lockIS 291Stainless SteelIS 291
Waterway/Barrel/PipeSeamless Tube IS 1239 (Part 2), IS 11428Cast Stainless SteelIS 318 LTB-II / IS 28 Gr. II
Handle hand wheelIS 1732, IS 210IS 1732, IS 210IS 1732, IS 210
NozzleIS 617 Gr 4450/4225, IS 318 LTB-II, IS 28 Gr. IIIS 3444IS 318 LTB-II / IS 28 Gr. II
Jet ratio controllerIS 318 LTB-II, IS 28 Gr. IIStainless SteelIS 318 LTB-II / IS 28 Gr. II
Drain valveIS 2004Stainless SteelIS 778

Additional Notes

  • Material selection must consider compatibility between purchaser and manufacturer.
  • Steel parts in contact with water: hot dip galvanized ≥ 0.03 mm thickness.
  • Aluminium parts in contact with water: hard anodized ≥ 0
5Construction and Design Requirements▼

IS 15811: Construction & Design Requirements for Water Foam Monitors

Key Specifications & Materials (Clause 4.1, Table 1)

ComponentCarbon Steel WaterwayStainless Steel WaterwayCopper Alloy Waterway
Inlet flangeIS 2002 Gr. I, IS 2004IS 6911IS 318 Gr. LTB-II, IS 28 Gr. II
ReducerIS 1239 (Part 2), IS 11428Stainless SteelIS 318 Gr. LTB-II, IS 28 Gr. II
Elbow/BendIS 4310Stainless SteelIS 318 Gr. LTB-II, IS 28 Gr. II
Swivel joint & worm wheelIS 318 LTB-II, IS 28 Gr. IIIS 318 LTB-II, IS 28 Gr. IIIS 318 Gr. LTB-II, IS 28 Gr. II
Worm shaftStainless SteelStainless SteelStainless Steel
Manual lockIS 291Stainless SteelIS 291
Waterway/Barrel/PipeSeamless Tube, IS 1239 (Pt 2)Seamless SS, Cast Stainless SteelIS 318 LTB-II, IS 28 Gr. II
Handle hand wheelIS 1732, IS 210IS 1732, IS 210IS 1732, IS 210
NozzleIS 617 Gr 4450/4225, IS 318 LTB-IIIS 3444IS 318 LTB-II, IS 28 Gr. II
Jet ratio controllerIS 318 LTB-II, IS 28 Gr. IIStainless SteelIS 318 LTB-II, IS 28 Gr. II
Drain valveIS 2004Stainless SteelIS 778

Construction & Operation (Clause 5.3)

  • 100-150 NB monitors: Worm and worm wheel type for vertical & horizontal traversing.
  • 63-80 NB monitors: Manual lock
6Workmanship and Finish▼

IS 15811: Workmanship and Finish (Clause 6) Key Points

  • Good workmanship and finish: All assemblies must be free from burns, sharp edges, and defects.
  • Smooth waterway finish: Essential to reduce friction loss and ensure efficient flow.
  • Material & Surface Treatment:
    • Steel parts in contact with water: Hot dip galvanized (min. 0.03 mm thickness).
    • Aluminium parts: Hard anodized (min. 0.015 mm thickness).
  • Leakage Testing (Clause 8.2):
    • Jet ratio controller tested hydraulically at 2.3 N/mm² for 5 min with no leakage.
  • Performance (Clause 9 & Table 2):
    • Monitor tested at 0.7 N/mm² pressure.
    • Spray/fog angle ≥ 120°.
    • Induction rate: 3-4% (for 3% requirement), 6-7% (for 6% requirement).
    • Expansion ratio:
      • Non-aspirating ≥ 1:4
      • Aspirating ≥ 1:6 (per IS 4989).
    • Effective reach (water and foam) given by Table 2, with aspirating type reach 10% less.

Table 2: Minimum Performance Requirement (Excerpt)

Monitor Size (mm)Water Discharge (LPM)Effective Water Reach (m)Effective Foam Reach (m)
6317505345
10035006456
150100008274

Summary Diagram: Workmanship & Finish Flow

flowchart TD
    A[Assembly Fabrication] --> B[Check for Burns & Sharp Edges]
    B --> C[Smooth Finish on Waterway]
    C --> D[Apply Anti-Corrosive Treatment]
    D --> E[Hot Dip Galvanizing / Hard Anodizing]
    E --> F[Leakage Testing at 2.3 N/mm²]
    F --> G[Performance Testing at 0.7 N/mm²]
    G --> H[Verify Induction & Expansion Ratios
7Anti-Corrosive Treatment▼

IS 15811: Anti-Corrosive Treatment (Clause 7) Summary

  • Steel components in direct water contact:

    • Must be hot dip galvanized after fabrication.
    • Minimum zinc coating thickness: 0.03 mm.
    • Thickness measured by suitable thickness meter.
  • Aluminium parts in direct water contact:

    • Must be hard anodized.
    • Minimum anodizing thickness: 0.015 mm.
  • Sea water use restriction:

    • Aluminium and carbon steel parts shall not be used due to corrosion risk.

Additional Notes from IS 15811:

MaterialAnti-Corrosive TreatmentMinimum Thickness
Carbon Steel (water contact)Hot dip galvanizing0.03 mm
Aluminium (water contact)Hard anodizing0.015 mm

Why this matters:

  • Hot dip galvanizing provides zinc sacrificial protection to steel, preventing rust.
  • Hard anodizing increases corrosion resistance and surface hardness of aluminium.
  • Avoiding aluminium and carbon steel in seawater prevents rapid corrosion.

Quick Visual Summary:

flowchart TD
    A[Steel Components] -->|Hot dip galvanize| B[Zinc Coating 0.03 mm]
    C[Aluminium Parts] -->|Hard anodize| D[Anodize Coating 0.015 mm]
    E[Sea Water Use] -->|No| F[Aluminium & Carbon Steel parts]

For detailed corrosion protection, always verify coating thickness with calibrated meters and ensure compliance with IS 15811 Clause 7.

8Leakage Testing▼

IS 15811: Leakage Testing & Performance of Water Foam Monitors

Leakage Testing (Clause 8)

  • Hydraulic Pressure: 2.3 N/mm² for 5 minutes.
  • Test Procedure:
    • Rotate horizontally 5 times clockwise and 5 times anti-clockwise.
    • Rotate vertically up and down for 5 cycles.
  • Acceptance: No leakage in any swivel joints or assembly parts.
  • Jet Ratio Controller (if provided): Tested separately at 2.3 N/mm² for 5 minutes with no leakage.

Performance Requirements (Clause 9 & Table 2)

  • Test Pressure: 0.7 N/mm² at monitor inlet flange.
  • Flow & Induction Rate:
    • Total flow = flow + induction rate.
    • Induction rate: 3-4% for 3% requirement; 6-7% for 6% requirement.
  • Expansion Ratio:
    • Non-aspirating: ≥ 1:4
    • Aspirating: ≥ 1:6 (measured per IS 4989)
  • Spray/Fog Angle: Minimum 120°
  • Effective Reach: Overall reach minus 5%.
  • Water & Foam Reach (m) at 30° nozzle elevation:
Monitor Size (mm)Water Discharge (LPM)Min Water Reach (m)Min Foam Reach (m)
6317505345
752580 - 300060 - 6252 - 54
1003500 - 415064 - 6856 - 60
1504750 - 1250069 - 9061 - 80

Note: For aspirating types, reduce reach by 10%.


Summary Diagram: Leakage Test Procedure

flowchart LR
    A[Start Hydraulic Test] --> B[Apply 2.3 N/mm² pressure for 5 min]
    B --> C[Rotate Horizontally 5x CW & 5x CCW]
    C --> D[Rotate Vert
9Performance Requirements▼

IS 15811: Performance Requirements for Water Foam Monitors

Key Specifications (Clause 9 & Table 2)

  • Test Pressure: 0.7 N/mm² at monitor inlet flange for flow, induction, and reach tests.
  • Induction Test: Use water.
  • Expansion & Foam Jet Reach Test: Use foam concentrate.
  • Spray/Fog Angle: Minimum 120°.
  • Flow Tolerance: Total flow within +5% / -0%.
  • Induction Rate:
    • 3% induction: 3% to 4% actual
    • 6% induction: 6% to 7% actual
  • Expansion Ratio:
    • Non-aspirating: ≥ 4:1
    • Aspirating: ≥ 6:1 (per IS 4989)
  • Paint: Fire red shade No. 536 or 538 (IS 5), paint per IS 2932.

Table 2: Minimum Performance Requirements

Monitor Size (mm)Water Discharge (LPM)Effective Water Reach (m)Effective Foam Reach (m)
6317505345
7525806052
7530006254
10035006456
10038006658
10041506860
15047506961
15056807264
15075007464
15080007666
150100008274
150125009080

Note: Aspirating types have 10% less reach than above.


Leakage & Hydraulic Testing (Clause 8.1 &

10Marking▼

IS 15811: Marking Requirements for Water Foam Monitors

Key Marking Specifications (Clause 12.1)

Each water foam monitor must be clearly and permanently marked with:

  • Manufacturer's name and trade-mark
  • Nominal size (mm)
  • Serial number
  • Year of manufacturing
  • Maximum working pressure (N/mm²)
  • Flow at specified pressure and foam concentrate induction rate

BIS Certification Mark (Clause 12.2)

  • The monitor may bear the BIS Standard Mark.
  • Use of the Standard Mark is governed by the Bureau of Indian Standards Act, 1986.
  • Licensing conditions for the Standard Mark are available from BIS.

Rounding Off (General Clause)

  • Test results and values must be rounded off as per IS 2:1960.
  • Retain the same number of significant digits as specified in the standard.

Summary Table for Marking Details

Marking ItemDescription
Manufacturer's name & markIdentifies producer
Nominal sizeSize in millimeters (mm)
Serial numberUnique ID for traceability
Year of manufactureManufacture year
Max working pressureIn N/mm²
Flow & foam induction ratePerformance parameters

For licensing and use of BIS mark, contact BIS regional offices listed in the standard.

flowchart TD
    A[Water Foam Monitor] --> B[Permanent Marking]
    B --> C[Manufacturer Name & Mark]
    B --> D[Nominal Size (mm)]
    B --> E[Serial Number]
    B --> F[Year of Manufacture]
    B --> G[Max Working Pressure (N/mm²)]
    B --> H[Flow & Foam Induction Rate]
    B --> I[BIS Standard Mark (optional)]

Note: Refer IS 2:1960 for rounding rules when reporting test values.

11Accessories▼

IS 15811: Accessories - Key Specifications & Tables


1. Accessories Specification:

  • Nozzle spanner is mandatory accessory.
  • Water foam monitor must be painted fire red (Shade No. 536 or 538 as per IS 5).
  • Paint shall conform to IS 2932.
  • Jet ratio controller (if provided) must be hydraulically tested at 2.3 N/mm² for 5 min with no leakage.

2. Material of Construction (Table 1):

ComponentCarbon Steel WaterwayStainless Steel WaterwayCopper Alloy Waterway
Inlet flangeIS 2002 Gr. I, IS 2004IS 6911IS 318 Gr. LTB-II, IS 28 Gr. II
ReducerIS 1239 (Part 2), IS 11428Stainless SteelIS 318 Gr. LTB-II, IS 28 Gr. II
Elbow/BendIS 4310Stainless SteelIS 318 Gr. LTB-II, IS 28 Gr. II
Swivel joint/worm wheelIS 318 LTB-II, IS 28 Gr. IIStainless SteelIS 318 Gr. LTB-II, IS 28 Gr. II
Worm shaftStainless SteelStainless SteelStainless Steel
Manual lockIS 291Stainless SteelIS 291
Waterway/Barrel/PipeSeamless Tube, IS 1239 (Part 2), IS 11428Cast Stainless SteelIS 318 LTB-II, IS 28 Gr. II
Handle hand wheelIS 1732, IS 210IS 1732, IS 210IS 1732, IS 210
NozzleIS 617 Gr 4450/4225, IS 318 LTB-II, IS 28 Gr. IIIS 3444IS 318 LTB-II, IS 28 Gr. II
Jet ratio controllerIS 318 LTB-II, IS 28 Gr.
12Certification Marking▼

IS 15811 - Certification Marking (Clause 12.2 & 12.1)

  • Certification Marking: Use of the BIS Standard Mark on monitors is governed by the Bureau of Indian Standards Act, 1986, and related rules.
  • Conditions for License: Manufacturers must obtain a license from BIS to use the Standard Mark. Details are available from BIS offices.
  • Mandatory Markings on Water Foam Monitors (Clause 12.1):
    • Manufacturer's name and trade-mark
    • Nominal size (in mm)
    • Serial number
    • Year of manufacture
    • Maximum working pressure (N/mm²)
    • Flow at specified pressure and foam concentrate induction rate

Summary Table for Marking Requirements

Marking ItemDescription
Manufacturer's name & trade-markIdentification of producer
Nominal sizeSize in millimeters
Serial numberUnique product ID
Year of manufactureProduction year
Maximum working pressureIn N/mm² (MPa)
Flow & foam induction ratePerformance parameters

Notes:

  • Markings must be clear and permanent.
  • Rounding off numerical values follows IS 2:1960.

For licensing and detailed conditions, contact BIS regional offices listed in the standard.

flowchart LR
    A[Manufacturer] --> B[Apply for BIS License]
    B --> C{License Granted?}
    C -->|Yes| D[Use BIS Standard Mark]
    C -->|No| E[No Marking Allowed]
    D --> F[Mark product with:]
    F --> G[Name & Trade-mark]
    F --> H[Nominal Size (mm)]
    F --> I[Serial Number]
    F --> J[Year of Manufacture]
    F --> K[Max Working Pressure (N/mm²)]
    F --> L[Flow & Foam Induction Rate]

This ensures compliance with IS 15811 certification marking requirements.

Annex AList of Referenced Indian Standards▼

IS 15811: List of Referenced Indian Standards

The standard references multiple Indian Standards critical for materials and components used in firefighting and related engineering fields. Key referenced IS include:

IS No.Title
IS 5:2004Colours for ready mixed paints and enamels (5th revision)
IS 28:1985Phosphor bronze ingots and castings (4th revision)
IS 210:1993Gray iron castings - Specification (4th revision)
IS 291:1989Naval brass rods and sections for machining purposes (3rd revision)
IS 2002:1992Steel plates for pressure vessels for intermediate and high temperature service including boilers (2nd revision)
IS 2643:2005Pipe threads where pressure-tight joints are not made on the threads
IS 617:1994Aluminium and aluminium alloy ingots and castings for general engineering purposes (3rd revision)
IS 3444:1999Corrosion resistant high alloy steel and nickel base castings for general applications (3rd revision)
IS 778:1984Copper alloy gate, globe and check valves for water works purposes (4th revision)
IS 1239:1990 (Part 1 & 2)Steel tubes, tubular and other wrought steel fittings - Specification
IS 4989:2006Foam concentrate for producing mechanical foam for fire fighting - Specification
IS 6911:1992Stainless steel plate, sheet and strip (1st revision)
IS 11428 (Parts 1 to 3)Specification for wrought carbon steel butt-welding pipe fittings
IS 1732:1989Dimension for round and square steel bars for structural and general engineering purposes (2nd revision)

Important Notes:

  • The Standard Mark usage is governed by the BIS Act, 1986 (Clause 12.2.1).
  • For detailed specifications, always refer to the latest edition of each referenced IS.
  • Rounding of values should comply with IS 2:1960.

Summary Diagram (Mermaid.js)

graph TD

Popular Questions About IS 15811

?What materials are specified for the construction of water-cum-foam monitors under IS 15811?▼

Under IS 15811, the materials for water-cum-foam monitors depend on the waterway material type: Carbon Steel, Stainless Steel, or Copper Alloy. Table 1 (Clause 4.1) specifies:

ComponentCarbon Steel WaterwayStainless Steel WaterwayCopper Alloy Waterway
Inlet flangeIS 2002 Gr. I, IS 2004IS 6911IS 318 Gr. LTB-II, IS 28 Gr. II
ReducerIS 1239 (Part 2), IS 11428Stainless SteelIS 318 Gr. LTB-II, IS 28 Gr. II
Elbow/BendIS 4310Stainless SteelIS 318 Gr. LTB-II, IS 28 Gr. II
Swivel joint & worm wheelIS 318 LTB-II, IS 28 Gr. IIIS 318 LTB-II, Stainless SteelIS 318 Gr. LTB-II, IS 28 Gr. II
Worm shaftStainless SteelStainless SteelStainless Steel
Manual lockIS 291Stainless SteelIS 291
Waterway/Barrel/PipeSeamless tube, IS 1239 (Part 2), IS 11428Seamless Stainless Steel, Cast SSIS 318 LTB-II, IS 28 Gr. II
Handle hand wheelIS 1732, IS 210IS 1732, IS 210IS 1732, IS 210
NozzleIS 617 Gr 4450/4225, IS 318 LTB-II, IS 28 Gr. IIIS 3444IS 318 LTB-II, IS 28 Gr. II
Jet ratio controllerIS 318 LTB-II, IS 28 Gr. IIStainless SteelIS 318 LTB-II, IS 28 Gr. II
Drain valveIS 2004Stainless SteelIS 778

Note: Material selection should be agreed upon between purchaser and manufacturer considering compatibility

?How does the standard define performance requirements for foam induction and water reach?▼

IS 15811 Performance Requirements for Foam Induction and Water Reach:

  • Test Pressure: 0.7 N/mm² at monitor inlet (base/mating/flange).
  • Water for Induction Test: Use water only.
  • Foam for Expansion & Jet Reach Test: Use foam concentrate.
  • Effective Reach: Overall reach minus 5% (still air condition).
  • Spray/Fog Angle: Minimum 120°.
  • Flow Tolerance: Total flow ±5% (no negative tolerance).
  • Induction Rate:
    • For 3% induction: 3% to 4%
    • For 6% induction: 6% to 7%
  • Expansion Ratio (per IS 4989):
    • Non-aspirating: ≥ 1:4
    • Aspirating: ≥ 1:6
  • Horizontal Reach (at 30° elevation): See Table 2 below (water & foam reach in meters).
Monitor Size (mm)Water Discharge (LPM)Effective Water Reach (m)Effective Foam Reach (m)
6317505345
752580 - 300060 - 6252 - 54
1003500 - 415064 - 6856 - 60
1504750 - 1250069 - 9061 - 80

Note: For aspirating types, reduce reach by 10%.


Loading diagram…

This ensures reliable foam induction and effective water/

?What types of nozzles are covered and how do they differ in operation?▼

Types of Nozzles Covered in IS 15811:

  1. Aspirating (Foam) Nozzle:

    • Consists of two main parts: body and barrel.
    • Body houses the water nozzle, diffuser, and foam inlet.
    • Barrel size (diameter & length) is designed for desired foam performance.
    • Foam is aspirated (mixed with air) before discharge, producing a foam jet or spray/fog.
  2. Non-Aspirating Nozzle:

    • Available in jet and spray/fog types.
    • Allows quick changeover between jet and full spray/fog under flow.
    • Has threaded or flanged inlet compatible with water foam monitor outlets.
    • Inducts foam concentrate directly without air aspiration.
  3. Additional Features:

    • Nozzles may have fixed or spinning teeth rings to improve fog application.
    • Spinning teeth can be metallic or non-metallic.
    • Optional jet ratio controllers ensure proper foam concentrate induction.

Operational Differences:

FeatureAspirating NozzleNon-Aspirating Nozzle
Foam MixingAir is aspirated with foam mixFoam concentrate mixed directly
Spray TypeJet and spray/fog via barrelJet and spray/fog with quick changeover
ConstructionBody + barrelSingle body with threaded/flanged inlet
ApplicationProduces expanded foamProduces foam/water spray or jet

Summary: Aspirating nozzles mix air to expand foam, ideal for thick foam blankets. Non-aspirating nozzles inject foam concentrate directly, offering flexibility between jet and fog spray patterns.

Loading diagram…

This diagram shows the flow paths for aspirating and non-aspirating nozzles.

?What are the testing procedures for leakage and hydraulic pressure compliance?▼

IS 15811 Leakage and Hydraulic Pressure Testing Procedure:

  • Test Pressure: 2.3 N/mm² (23 bar)
  • Duration: 5 minutes
  • Procedure:
    • Subject the entire assembly to hydraulic pressure of 2.3 N/mm².
    • During the test:
      • Rotate horizontally 5 times clockwise and 5 times anti-clockwise.
      • Move vertically up and down for 5 cycles.
    • Observe for any leakage at swivelled joints—no leakage allowed.
  • Jet Ratio Controller (if provided):
    • Also tested at 2.3 N/mm² for 5 minutes.
    • No leakage allowed.

Post Leakage Test:

  • Perform performance tests at 0.7 N/mm² for flow, induction rate, and horizontal reach as per Table 2.

Summary Table: Leakage Test

ParameterValue
Hydraulic Pressure2.3 N/mm²
Test Duration5 minutes
Horizontal Rotation5 cycles CW & CCW
Vertical Movement5 cycles up/down
LeakageNone allowed

This ensures hydraulic integrity and no leakage under operational stresses.

Loading diagram…
?How is corrosion resistance ensured for monitors used with sea water?▼

Corrosion Resistance for Monitors Used with Sea Water (IS 15811)

  • Aluminium and carbon steel parts are prohibited for sea water service (Clause None).
  • Waterway materials must be corrosion-resistant:
    • Use stainless steel or copper alloys for waterways and components exposed to sea water (Clause 4.1 & Table 1).
  • Joints:
    • Welded, screwed, or flanged joints are used for stainless steel or copper alloy waterways (Clause 5.1).
    • Screwed joints have a minimum 20 mm thread length, sealed with epoxy-based sealant and locked with grub screws to prevent loosening.
  • Components like swivel joints, worm wheels, worm shafts, and nozzles are specified in corrosion-resistant materials (stainless steel or copper alloys).
  • Material selection must ensure compatibility and resistance to sea water corrosion as agreed between purchaser and manufacturer (Clause 4.1 Note).

Summary Table Extract (Material for Sea Water Monitors):

ComponentStainless SteelCopper Alloy
Waterway/Barrel/PipeCast StainlessIS 318 Gr. LTB-II, IS 28 Gr. II
NozzleIS 3444IS 318 Gr. LTB-II, IS 28 Gr. II
Worm ShaftStainless SteelStainless Steel
Swivel JointStainless SteelIS 318 Gr. LTB-II

Key: Avoid carbon steel/aluminium; use stainless steel or copper alloys for durability in sea water.

?What are the requirements for the horizontal and vertical traversing mechanisms?▼

According to IS 15811, the requirements for horizontal and vertical traversing mechanisms of water foam monitors are:

  • Horizontal rotation: 360° continuous rotation (clockwise and anti-clockwise) via a swivel joint.
  • Vertical rotation: Minimum 135° total (90° upward + 45° downward).

Traversing Mechanism Types:

  • Single handle bar type with manual positive locks for unattended operation.
  • Worm and worm wheel type with irreversible self-locking for unattended operation.

Size-specific requirements:

Monitor Size (NB)Traversing Mechanism Type
63 & 80 NBManual lock or worm and worm wheel (vertical & horizontal)
100 to 150 NBWorm and worm wheel type (vertical & horizontal)

Additional Notes:

  • The assembly must withstand hydraulic pressure of 2.3 N/mm² for 5 minutes with no leakage.
  • During pressure testing, horizontal rotation is done 5 times each way, and vertical rotation is cycled 5 times.

Loading diagram…

This ensures reliable, smooth, and locked positioning for firefighting operations.

?How should the water-cum-foam monitor be marked according to this standard?▼

According to IS 15811 Clause 12.1, each water-cum-foam monitor must be clearly and permanently marked with the following minimum details:

  • Manufacturer's name and trade-mark
  • Nominal size (in mm)
  • Serial number
  • Year of manufacturing
  • Maximum working pressure (in N/mm²)
  • Flow at specified pressure
  • Foam concentrate induction rate

Additional Notes:

  • The nominal size refers to the waterway diameter.
  • The monitor is designed for a minimum rated pressure of 1.2 N/mm².
  • Markings ensure traceability and confirm performance parameters.

This marking ensures compliance, operational safety, and ease of identification during maintenance or inspection.

Loading diagram…
✦

Need Detailed Clause Answers?

Ask AI about any clause, requirement, or provision in IS 15811. Get instant, clause-cited responses powered by our indexed library.

Free tier includes 150 queries (50 AI + 100 Reference) · No credit card required